Basic Documentation

194/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Sequence controller 03.10.2011
Main menu > Commissioning > Extra configuration > Controller 1...3 > Outputs \ \ \_ >
Operating line Adjustable values / remarks
[Sequence 1] load ---, Modulating output A..D, Step switch 1..5, Heat recovery equipment, Mixed air damper
[Sequence 1] pump ---, Pump 1...4
[Sequence 2] load ---, Modulating output A..D, Step switch 1..5, Heat recovery equipment, Mixed air damper
[Sequence 2] pump ---, Pump 1...4
[Sequence 3] load¹
)
---, Modulating output A..D, Step switch 1..5, Heat recovery equipment Mixed air damper
[Sequence 3] pump¹
)
---, Pump 1..4
¹
)
only available in controller 1
Main menu > Commissioning > Extra configuration > Controller 1...3 > Outputs _/ / >
Operating line Adjustable values / remarks
[Sequence 4] load ---, Modulating output A..D, Step switch 1..5, Heat recovery equipment, Mixed air damper
[Sequence 4] pump ---, Pump 1..4
[Sequence 5] load¹
)
---, Modulating output A..D, Step switch 1..5, Heat recovery equipment, Mixed air damper
[Sequence 5] pump¹
)
---, Pump 1..4
¹
)
only available in controller 1
A sequence is activated by assigning either a load output or pump output to it. If
none of the 2 is assigned to a sequence, this sequence and all subsequent
sequences are inactive.
15.1.2 Load outputs
Load outputs are:
Modulating output A…D
Heat recovery equipment
Mixing damper
Step switch 1…5
Only one load output can be assigned to each sequence. Each load output can be
controlled by max 2 to 3 sequences (depending on function block).
Cooling and dehumidification.
B
A
y1 y2 y3
y1 y2 y3
A
B
730
720
Mod output
Mod output
The sequence controller is not suited for delivering more cooling via the second fan
speed because supply air temperature control overrides the sequences!
A second room temperature controller step can be entered directly at the cascade
controller (see section 11.6.3).
Config
uration
Application example
Note