Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Sequence controller 03.10.2011
No. Text Effect
3101 [Controller 1] inadm
deviation
Non-urgent message; must not be
acknowledged
3102 [Controller 2] inadm
deviation
Non-urgent message; must not be
acknowledged
3103 [Controller 3] inadm
deviation
Non-urgent message; must not be
acknowledged
Basic type C: Chilled water flow temperature control.
With an upward adjustment of the setpoint, the water can take a very long time to
warm up if the valves are closed and the pipe is well insulated. Here, the message
delay is set to 10 hours in order to avoid unnecessary fault status messages. It is
very likely that the valves do not close properly, if, after 10 hours, there is still a
setpoint deviation.
15.8 Control timeout
You can define a control timeout period (TIMEOUT) in order, for example, to
prevent the cooling valve from opening immediately after the heating valve closes.
The controller does not add the integral action component during that period of
time.
Main menu > Commissioning > Settings > … or
Main menu > Settings > Controller 1...3 > Control parameters >
Operating line Range Factory setting
Control timeout 00.00…59.55 m:s 00.00 m:s
15.9 Assign texts
A text can be assigned to each controller. This text appears on the menu and in the
operating line.
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Controller 1…3 >
Operating line Range Factory setting
Controller x Max. 20 characters Controller x
Refer to section 31.4 for an overview of all editable texts and on how to reset them.
Fault status messages
Application example
Setting values
Free text