Basic Documentation

22/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Philosophy of basic types 03.10.2011
Individual room control functions are described in the documentation P3127
As an option, the following information can be defaulted for individual room
control during configuration:
Room operating mode with time program.
Timer function.
Operating mode selector.
Holidays and special days.
Fire shutdown and smoke extraction.
For details, refer to the basic documentation for the RMB795 (P3121).
3.3 Basic type C, chilled water treatment
Typical field of use: Demand-dependent of chilled water treatment.
T
3150S03
V
Control of chilled water treatment with a RMU7..B as primary controller; chilled
water consumers include the air cooling cool for the ventilation plants or chilled
ceilings with individual room control. The controllers connected via KNX and
exchange the relevant operating data.
Special case: Chilled water and domestic hot water for a 2-pipe system with
heating/cooling changeover. Details described in section 27 "Heating/cooling
cha
ngeover".
Operating mode: Demand-dependent by KNX signal.
The chilled water treatment is switched on and off via the demand signals
(refrigeration distribution zones) for the individual room controllers.
Use of Controller 1: To demand-dependent setpoints by KNX signal.
The flow temperature controller works with a flow setpoint; connected individual
room controllers provide or coordinate the flow setpoints.
The following aggregates/functions cannot be configured for this basic type:
Fans, heat recovery equipment, mixed air damper, frost protection, preheating
function, sustained mode and night cooling
Room device QAW740 cannot be used with basic type C
Features of individual
room control
Example: Demand-
dependent flow
temperature control
Features of basic type C
Notes