19.3.2 Sustained mode (Economy) for cooling
The example refers to controller 1 with a main controlled variable for room
temperature. It can be functionally be applied to controller 2 and controller 3.
At the end of occupancy, the plant switches off, i.e. the plant operating mode
changes from normal operation (Comfort) to sustained mode (Economy). The room
temperature falls or rises depending on the prevailing weather conditions and the
climatic conditions in the room.
If the room temperature exceeds the Economy cooling setpoint, sustained mode
cooling results.
In sustained mode, cooling is provided until the room temperature drops 1 Kelvin
below the Economy cooling setpoint. The plant is again switched off.
1 K
Smin
SpCEco
SpCEco
End of
Co
mf
o
rt
Comfort Comfort
RT
[°C]
Plant component state
In Economy mode, the plant is switched on when the room temperature drops
below the set Economy heating setpoint (SpHEco). When the plant operates, the
set Comfort setpoints are maintained (fan speeds and setpoints of all control
loops).
Sustained mode can only be activated when there are no fault messages that
switch off the plant.