232/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Night cooling (basic type A) 03.10.2011
22
23
24
25
21
20
19
18
T
[°C]
t
t
Nmin
SpHComf + 1 K
OT limit
Precooling time max
End of
Comfort
Beginning of
Comfort
Room-outside temp delta
3150D08en
RT actual value
OT actual value
Night cooling
SpHComf + 1 K Comfort heating setpoint plus 1 K t
Nmin
Operating time min
OT limit value Outside temperature limit value
21.3 Troubleshooting
Monitoring room temperature is described in section 8.5; monitoring of outside
temperature in section 8.4.
If both room temperature and outside temperature are not available, "Night cooling"
is deactivated.