Basic Documentation

24/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Commissioning 03.10.2011
4 Commissioning
Preparation for use and commissioning of Synco™ 700 controllers must only be
undertaken by qualified staff who have been appropriately trained by Siemens
Building Technologies.
4.1 Enter commissioning mode
During commissioning, both control and plant safety functions remain deactivated!
4.1.1 Introduction during initial power-up
The language menu appears the first time power is supplied to the controller.
Select the language for commissioning and operating the plant.
After the language is selected and confirmed with the OK knob, the time of day,
date and year can be set in the same way.
The commissioning menu then appears. The access level is set to "Password
level". The "Plant type" menu (path: Main menu > Commissioning > Basic
configuration > Plant type) offers the commissioning engineer a number of plant
types for selection. When commissioning the controller for the first time, the
procedure given in the Installation Instructions 74 319 0731 0 (G3151xx) must be
followed. They are enclosed with the controller.
4.1.2 Entry from the main menu
After selecting operating line "Commissioning" (only visible on the "Password
level") and confirming by pressing the OK knob, a reference to plant stop appears
on the display.
Caution!
Plant stops
ESC OK
After pressing the OK knob again, the plant (application) stops. All outputs are set
to a defined OFF state and the display shows the "Commissioning" menu.
Commissioning
Basic configuration...
Extra configuration...
Settings…
Communication…
Setting level:
Commissioning menu