Basic Documentation

240/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Fan speed controller, demand-controlled (basic type P) 03.10.2011
Variant with constant room overpressure control
Setting values must be adapted accordingly, if the extract air fan is implemented as
constant room overpressure control (e. g. pressure setpoint = 25 Pa, setpoint
reduction = 0 Pa etc.).
The rate at which pressure setpoints or speed are optimized is defined via the
"Control action" setting parameter.
In addition, you can also define how to evaluate the collected damper positions.
Maximum: Only the highest damper position is considered for setpoint
compensation.
Average: The average of all damper positions is considered for setpoint
compensation.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Supply air fan >
Operating line Range Factory setting
Control action Slow, Medium, Fast Medium
Request evaluation Maximum, Average Maximum
These settings are entered for Supply air fan and apply as well for the Extract air
fan.
The value for the "geographic zone (Apartment" must be set if the local time
switch 1 is active on the RMU controller. Additional information is available in
Section 28.2.2 (Sub-menu "Room")
The setting value "Air distribution zone" defines assignment of individual room
controllers to the corresponding primary air handling unit. Additional information
is available in Section 28.2.5 (Sub-menu "Distribution zone")
Control action
Evaluation of request
Setting values
Required settings