Basic Documentation

242/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Fan speed controller, demand-controlled (basic type P) 03.10.2011
Primary air handling unit with supply/extract air fan
Individual room control (RDG400KN) for VAV single duct system with supply air
compact controller with analog damper position signal.
Data exchange between the primary air handling unit and the individual room
controllers via KNX with the following functions:
Optimization of the pressure setpoints for supply air and extract air using the
damper positions VAV supply air compact controller.
Demand-controlled plant operation and optimization of the supply air setpoint by
heat and refrigeration demand signals.
~
KNX
T
MV
.
f1
f2
RMU-B
KNX
M
M
~
f1
f2
p
p
Configuration overview
Primary air handling unit RMU7x0B
Setting values Supply air
Fan
Extract air
Fan
Control mode Duct pressure (DP stat) Duct pressure (DP stat)
Pressure optimization Supply-extract air in parallel
Pressure setpoint 220 Pa 230 Pa
Pressure setpoint reduction 160 Pa 160 Pa
VAV supply air damper position (0…100%) VAV extract air damper position
(0…100%).
Demand-controlled supply air temperature control
Supply air limit value max 26°C
Supply air limit value min 15°C
Supply air heat demand (0…100%)
Supply air refrigeration demand (0…100%)
Individual room control RDG400KN, VAV controller G…B181.1E
Supply air Extract air
Assignment VAV Yes No
Damper position signal - type Yes - analog 0-10V DC via RDG400KN No
Setpoint compensation fans Yes Yes, common control signal from
VAV controller supply air
Example 2