Basic Documentation

247/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Faults 03.10.2011
24.3 Universal fault inputs (1…10)
Function block "Faults" has 10 universal fault inputs at its disposal. Any type of
analog or digital signal can be fed to these inputs.
Main menu > Commissioning > Extra configuration > Faults >
Operating line Adjustable values / remarks
Fault input 1 ---, N.X1, N.X2, ...
...
Fault input 10 ---, N.X1, N.X2, ...
The following settings are possible for each fault message:
Fault status signal delay.
Elapsed time until a pending fault generates a fault message
Fault acknowledgement
Impact of fault
Fault priority
Limit value "Fault on": Limit value from which the fault status message is
generated
Limit value "Fault off": Limit value for the normal state
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Faults > Fault input 1...10 >
Operating line Range Factory setting
Fault status message
delay
00.00...59.55 m:s 00.00 m:s
Fault
acknowledgement
None, Acknowledge,
Acknowledge and reset
None
Fault priority Urgent, Not urgent Not urgent
Impact of fault No stop, Stop No stop
Limit value fault on Depending on the selected
type
Depending on the type
Limit value fault off Depending on the selected
type
Depending on the type
If the upper and the lower limit of a measured value is to be monitored, the
signal must be fed to 2 fault inputs
To monitor the lower limit, the operating line "Limit value fault on" is set below
"Limit value fault off". This generates a fault message when the measured value
is lower than the "Limit value fault on"
The differential "Limit value fault on" and "Limit value fault off" represents the
hysteresis
If data point "Limit value fault on" is set equal to "Limit value fault off", no fault
message is generated
Connections
Configuration
Settings
Setting values
Notes