Basic Documentation

278/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Communication 03.10.2011
28.2.3 "Time switch 2" menu item
If the device is connected to other controllers via communication, time switch 2
rather than autonomous operation can be operated as slave (i.e. it receives the
time switch via bus).
Main menu > Commissioning > Communication > Time switch 2 >
Operating line Range Factory setting
Time switch slave (apartment) ----, 1..126 ----
Transformation Precomfort Off, On On
See section 7 for a detailed description of the operating lines.
28.2.4 "Holidays / special days" menu item
If the controller communicates with other controllers, the same holidays/special
days program can be assigned to other controllers.
Main menu > Commissioning > Communication > Holidays/special days >
Operating line Range Factory setting
Holidays/special day
operation
Autonomous, Slave,
Master
Autonomous
Holidays/special day zone 1...31 1
See section 6.10.1 for a detailed description of the operating lines
28.2.5 "Distribution zones" menu item
Main menu > Commissioning > Communication > Distribution zones >
Operating line Range Factory
setting
For basic
type
See section…
Outside temperature
zone
----, 1...31 ---- A, P, C, U 8.4.3
Air distribution zone ----, 1...31 1 P 3.2, 12.3 or
23.3
Heat distribution zone ----, 1...31 1 A, P, C
1)
, U 25.1 or 25.2
Heat distr zone source
side
----, 1...31 ---- C
1)
25.2
Heat demand setpoint
increase
0...50 0 K C
1)
25.2
Refrigeration
distribution zone
----, 1...31 1 A, P, C, U 26.1 or 26.2
Refrig distr zone
source side
----, 1...31 ---- C 26.2
Refrig demand setp
reduction
0...50 0 K C 26.2
1)
Only for basic type C and simultaneous H/C changeover
Setting values
Setting values
Setting values