Basic Documentation

28/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Commissioning 03.10.2011
4.6 Data backup
The entire commissioning data set (configuration and all settings) can be saved in
the controller after commissioning. If, any time later, an unauthorized person
readjusts important values, this function can be used to restore the proper
controlled state after commissioning.
The following values are not saved or restored during backup:
All user-defined texts and business cards
Calendar and time switch settings
Basic settings on the "Communication" menu
Current time of day
Trend settings
Values on the "Settings > Device" menu
Main menu > Data backup >
Operating line Range Factory setting
Restore
Save
Main menu > Data backup >
Operating line Comments
Storage date Display date for download of commissioning data set
to the controller’s memory
Storage year Display of the year for download of commissioning
date set to the controller’s memory
4.7 Exit password level
Set the access level on the controller to "User level" after completing
commissioning. Procedure:
1. Go to main menu
2. Press the OK knob and the ESC button at the same time. The "Access level"
menu appears
3. Select "User level" by turning the knob and press OK to confirm
Setting values
Display values