Basic Documentation

281/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Communication 03.10.2011
Reception zones Transmission zones
Inputs (N.X1…A8(2).X4) Inputs (N.X1…A8(2).X4)
Digital outputs (N.Q1…A8(2).Q5)
Analog outputs (N.Y1…A8(2).Y2)
Main menu > Commissioning > Communication > LTE reception zones >
Operating line Range Factory setting
N.X1…A8(2).X4 ---, 1…4095
1)
---
Main menu > Commissioning > Communication > LTE transmission zones >
Operating line Range Factory setting
N.X1… A8(2).X4
N.Q1…A8(2).Q5
N.Y1…A8(2).Y2
---, 1…4095
1)
---
1)
The following range data applies for the activated filter table function when using the universal
transmission and reception zones with line coupler or IP router:
1…3839 are blocked for data exchange.
3840…4095 are open for data exchange.
Bus signals can be simulated using the "Simulation inputs" function when
commissioning the plant (Section 8.1.3).
No. Te
xt Effect
5902 >1 identical LTE zone Non urgent message; must not be
acknowledged.
The air quality average for 2 air quality sensors are available on one RMS705B
(device 1) from 2 air quality sensors. This value is sent as a transmission object via
an analog output and processed from an RMU7x0B (device 2).
The following transmission and reception zones are engineered for example tasks:
RMS705B, device 1 RMU7x0B, device 2 Value
Terminal Transm.zone Terminal Reception zone
N.Y1 1 N.X1 1 Average for air quality
= Transmit
= Receive
In RMS705B, device 1, the following is configured:
Main menu > Commissioning > Communication > LTE transmission zones >
Operating line Range Factory setting
N.Y1 1
In RMU7x0B, device 2, the following is configured:
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line Range Factory setting
N.X1 ppm
Overview
Setting values
Setting values
Note
Fault status messages
Example 1
Data exchange concept
Configuration
Device 1
Device 2