Basic Documentation

283/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Communication 03.10.2011
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line Range Factory setting
N.X1 Digital
Main menu > Commissioning > Communication > LTE transmission zones >
Operating line Range Factory setting
N.Q2 2
Main menu > Commissioning > Communication > LTE reception zones >
Operating line Range Factory setting
N.X1 1
C
Zone 2
Zone 1
Logic 1
Unit 1
Unit 2
On one RMS705B (device 1), enthalpy values A, B are pending, calculated from
temperature and relative humidity. These values are sent as a transmission object
via the analog outputs and used in a second device by the mixed air damper or
heat recovery for the MECH function.
Adjust the value range of the receiving terminal (device 2) to the unchangeable
value range of the calculated enthalpy prior to use in device 2. The fixed default
value ranges for the enthalpy computer are available in Section 9.2 above (P3124).
The followi
ng transmission and reception zones are engineered for example tasks:
RMS705B, device 1 RMU7x0B, device 2 Value
Terminal Transm.zone Terminal Reception
zone
N.Y1 1 N.X1 1 Enthalpy value for
another application.
N.Y2 2 N.X2 2 Enthalpy value for
another application.
= Transmit
= Receive
Configuration diagram
Example 3
Note
Data exchange concept