Basic Documentation

297/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Appendix 03.10.2011
31.2.2 Overview of configuration diagrams
See the configuration diagram for assignment of inputs and outputs.
Basic configuration
Configuration Function
Plant type Basic type A: Room temperature ventilation controller (sequence controller 1 is a room temperature
controller, room/supply air temperature cascade controller or supply air temp controller)
Basic type P: Supply air temperature controller, demand-controlled (sequence controller 1 is supply air
temperature controller)
Basic type C: Flow temperature controller, demand-dependent (sequence controller 1 is a demand-
dependent chilled water flow temperature controller)
Basic type U: Universal controller (sequence controller 1 is a universal controller)
A01…A05: Select a programmed application (activate configuration stored in the controller)
RMZ785
RMZ787(1), (2)
RMZ788(1), (2)
Add further inputs and outputs with extension modules RMZ785, RMZ787, and RMZ788; controller
functions can be configured to these inputs/outputs
Specify which modules are connected to the controller in which order (position); max 4 modules
Input identifiers
Inputs
Section 8
Configuration Functions
N.X1
x
N.X1…RMZ788.X4
Enter input identifier
Units:
°C, %, g / kg, kJ /kg, W / m², m / s, bar, mbar, Pa, ppm, Universal
000.0 (display with one decimal place), Universal 0000 (display
without decimal place).
The unit is only required for presentation on the display. The unit
presents all unit-dependent settings (e.g. P-bands) on the unit.
Sensors for °C:
LG-Ni1000, 2xLG-Ni1000 (averaging), T1, Pt1000, DC 0…10 V,
all other units DC 0…10 V, adjustable range
Digital (input for potential-free contacts)
Special identifiers:
Room temperature, Outside temperature, Extract air temperature,
Supply air temperature, Frost protection, Remote setpoint
adjuster, Pulse.
With the special identifiers, internal connections are taken directly
from the controller
A name can be assigned to each input
N.X1
Y
SIGNAL Y
x
RT
Room temperature Only possible with basic type A, also in combination with room unit
(averaging), sensor as described under "Sensors for °C"
N.X1
Y
SIGNAL Y
x
OT
Outside temperature Outside temperature, sensor as described under "Sensors for °C", for
the following functions:
Summer/winter compensation
Sequence locking acc to OT
Pump on at low outside temperatures
Locking of fan speed 2 at low outside temperatures
Max limitation of the outside air damper at low outside
temperatures
N.X1
Y
SIGNAL Y
x
EAT
Extract air temperature Basic type A only, sensor as described under "Sensors for °C", for
the following functions:
Extract air temperature control, extract/supply air cascade control