Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Appendix 03.10.2011
N.X1
Y
SIGNAL Y
x
SAT
Supply air temperature Basic type A only, sensor as described under "Sensors for °C", for
the following functions:
Controlled variable for supply air temperature
N.X1
x
Frost protection Frost prot. function selectable for sequence controllers 1, 2, 3 for:
Water-side frost protection (input LG-Ni 1000) with 2 stages,
PI control when plant is switched off
Air-side frost protection (input DC 0…10 V = 0…15 °C) with 2
stages
Frost protection unit
Preheating function
N.X1
x
Frost protection unit 1
Frost protection unit 2
Frost protection unit 3
Frost protection unit, direct acting on corresponding sequence
controllers 1, 2, or 3
N.X1
x
[Controller 1] rem setp adj
[Controller 2] rem setp adj
[Controller 3] rem setp adj
Rem setp adjuster relative
Remote w1: Absolute for sequence controllers 1..3 (0..1000 or
DC 0...10 V)
Remote rel: Relative for room temperature with basic type A
sequence controller 1 (1000...1175 O = -3...+3 K)
N.X1
x
Pulse Select input identifier "Pulse" for an input.
Connection of a pulse source (mechanical or electronic)
Pulse source type can be assigned to the input
Open and closed-loop control functions
Controller
Section 11, 12, 13, 14
Configuration Functions
S3 S2 S1 S4 S5
yp yp yp yp yp
a
d
Controller 1
(Ventilation)
With supply air limitation
Cascade
Constant (supply air)
Cascade/const (alternating)
Seq. limit. Casc/Const
Controller 1, basic type A:
Sequence limiter (seq. limiter)
Casc/const changeover input
Sequence S1…S5 load (y)
Sequence S1…S5 pump (p)
Control strategy
Sequence controller, can be used as a P, PI or PID controller.
The following control modes are available:
Supply air temperature control
Room temperature control (with optional limitation of supply air)
Extract air temp. control (with optional limitation of supply air)
Room/supply air temperature cascade control
Extract air/supply air temperature cascade control
Configurable sequence assignments; one load output (modulating
output A…D, heat recovery unit, mixed air damper, step switch
1…5) and a pump can be connected to each sequence
Heating sequences S1, S2 and S3 (\\\_)
Cooling sequences S4 and S5 (_//)
Supply air temperature limiter acts on all sequences
Sequence limiter, adjustable as min or max limiter, acts on a
settable sequence (closing)
Sustained mode room temperature
Night cooling of room
fan speed at large heating or cooling load in room
Summer/winter compensation with outside temperature
Sequence locking acc to OT
Fault message for unacceptable control deviation can be
activated
S3 S2 S1 S4 S5
yp yp yp yp yp
aa aa
Gen limit Seq limit
Controller 1 (Primary supply air)
Controller 1 basic type P:
Universal shift ( )
General limiter (gen. limiter)
Sequence limiter (seq. limiter)
Sequence S1…S5 load (y)
Sequence S1…S5 pump (p)
Activate sequence controller dependent on demand, settable as P,
PI or PID controller, for demand-dependent supply air temperature
control related to individual room controller (supply air temperature
sensor readily wired to N.X1).
Configurable sequence assignments; one load output (modulating
output A…D, step switch 1…5) and a pump can be connected to
each sequence
Heating sequences S1, S2 and S3 (\\\_)
Cooling sequences S4 and S5 (_//)
Frost n
Pulse
Frost