Basic Documentation

299/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Appendix 03.10.2011
General limiter acts on all sequences
Sequence limiter, can be set as min or max limiter, acts on a
adjustable sequence (closing)
Universal shift
Sequence locking acc to OT
Fault message for unacceptable control deviation can be
activated
aa a
S3 S2 S1 S4 S5
yp yp yp yp yp
Gen limit Seq limit
Controller 1 (Flow temperature)
Controller 1 basic type C:
Universal shift ( )
General limiter (gen. limiter)
Sequence limiter (seq. limiter)
Sequence S1…S5 load (y)
Sequence S1…S5 pump (p)
Activate sequence controller dependent on demand, settable as P,
PI or PID controller, for demand-dependent flow temperature control
(chilled water or 2-pipe systems H/C) flow temperature sensor readily
wired to N.X1).
Configurable sequence assignments; one load output (modulating
output A…D, step switch 1…5) and a pump can be connected to
each sequence
Heating sequences S1, S2 and S3 (\\\_)
Cooling sequences S4 and S5 (_//)
General limiter acts on all sequences
Sequence limiter, can be set as min or max limiter, acts on a
adjustable sequence (closing)
Universal shift
Sequence locking acc to OT
Fault message for unacceptable control deviation can be
activated
aa a a a
S3 S2 S1 S4 S5
yp yp yp yp yp
Diff
Controller 1
Gen limit Seq limit
Controller 1 basic type U;
Controllers 2, 3 (basic types A, P,
C, and U):
Main controlled variable
Differential input (diff)
Universal shift ( )
General limiter (gen. limiter)
Sequence limiter (seq. limiter)
Sequence S1…S5 load (y)
Sequence S1…S5 pump (p)
Universal sequence controller, as P, PI or PID controller.
Configurable sequence assignments; one load output (modulating
output A…D, step switch 1…5) and a pump can be connected to
each sequence
Heating sequences S1, S2 and S3 (\\\_)
Cooling sequences S4 and S5 (_//)
Simple or differential controller
(setpoint linkable to sequence controller 1)
General limit controller acts on all sequences
Sequence limit controller, settable as min or max limiter, acts on a
settable sequence (closing)
Universal shift
Sequence locking acc to OT
Fault message for unacceptable control deviation can be
activated
IAQ controller.
Section 16
Configuration Functions
a
IAQ controller
Input Room air quality control
Open outside air damper
Switch on fans at poor air quality (Precomfort, Economy)
Changeover of fan speeds (with 2-speed fans)
Increase fan speed (speed-controlled fans without pressure
control)
Operating modes / Time switches
Operating mode
Section 6, 7
Configuration Functions
Basic types A and U:
Timer function ( )
Rm optg mode inp 1 ( )
Rm optg mode inp 2 ( )
Holiday input ( )
Special day input ( )
Room operating modes
Timer function: Digital input for room operating mode Comfort for
a settable period of time
Preselection of settable room operating mode with room operating
mode input 1
Room optg mode selector with room operating mode input 1+2