Basic Documentation

300/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Appendix 03.10.2011
Operating mode relay 1, 2 Holiday input and special day input: Digital input for holidays
(settable room operating mode) or special day (special day
program of time switch)
Settings for possible plant operation mode (e.g. sustained mode,
recirculated air mode)
Output of operating mode via relay contacts
d
d
d
dd
12
QQ
1
Relay
Yes
Time switch 1
Fire
SA EX
Basic type P:
Time switch (Yes, No)
Holiday input ( )
Special day input ( )
Fire alarm off ( fire)
Extract air ( Supply air,
Extract air)
Operating mode relay 1, 2
Time switch can be activated for other applications, acts on bus
Holiday input and special day input: Digital input for holidays
(settable room operating mode) or special day (special day
program of time switch)
Fire and smoke extraction inputs to control plants and signal to
individual room controller via bus
Output of operating mode via relay contacts
dd
12
QQ
1
Relay
Yes
Time switch 1
Basic type C:
Request input
Time switch (Yes, No)
Holiday input ( )
Special day input ( )
Operating mode relay 1, 2
Request input signal for external request signal refrigeration
Time switch can be activated for other applications, acts on bus
Holiday input and special day input: Digital input for holidays
(settable room operating mode) or special day (special day
program of time switch)
Output of operating mode via relay contacts
Q d
2
On / Off
On
Time switch (Yes, No) 1-channel time switch on / off
7 days + special day, 6 switching points per day
Note selectable holidays/special day information (Yes, No)
Operation selector
Heating / cooling changeover
Heating / cooling
changeover
Section 27
Configuration Functions
x
Q
23
H/C changeover
2-pipe system H/C ( )
H/C changeover input ( )
Changeover with operating
mode selector (
)
Changeover by date (
23
)
Changeover of operating mode heating or cooling in 2-pipe
systems
Preselection of heating/cooling on device generated or received
as signal via bus
Changeover by analog or digital input
Changeover with operating mode selector
Changeover by date
Faults
Faults
Section 24
Configuration Functions
QQ
xx
12
34
56
xxxxd
Ack
Faults
Relais1 Relais2
External fault button
Fault inputs 1 through 10
Fault relays 1 and 2
Filter supervision ( )
Fire alarm off ( fire)
Extract air ( Supply air,
Extract air)
Fan release relay
10 universal fault signal inputs, fault signal delay, fault
acknowledgement (none, acknowledge), fault priority (urgent, not
urgent) and fault effect (stop, no stop) can be set
2 fault relays, priority (urgent, not urgent, all) and signaling can be
set
Filter supervision, Fire alarm off and Smoke extraction
Fan release relay (if external fan switch, no release in case of fault
with plant stop; fans remain released with smoke extraction)
Direct connection possible for analog signals and settable
threshold values
A name can be assigned to each fault input