Basic Documentation

301/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Appendix 03.10.2011
Data acquisition
Trend
Section 9.1
Configuration Functions
Input
The trend is used to log the progression of signals.
4 independent trend channels
Logging of local inputs, room temperatures and outside
temperature from the bus
Simultaneous display of 2 channels
Views: 8-minutes, 8-hours, 24-hours and 6-day history
Meters
Section 9.2
Configuration Functions
1
2
i
i
Meter
Input Acquire pulse sources and display cumulated values; selectable
unit, valency, presentation, etc.
Aggregates
Supply air fan
extract air fan
Section 10.1
Configuration Functions
xxxx
QQQ
2
1
12
V
12
dx d
p
a
Y
Start Stop
Speed
Duct pressure (DP stat)
Vol flow (DP dyn)
Vol flow (linear 0..10 V)
Supply
Speed 1(1Q)
Speed 2 (2Q)
Speed (Y)
Precommand output ( )
Precommand checkback ( )
Pressure sensor (
p
)
Flow signal (
V
)
Overload signal ( )
Start condition 1 / 2
Stop condition 1 / 2
Can be used for single-speed, 2-speed or speed-controlled fans
Possible types of control for variable-speed fans:
Assign fixed speeds for 1 or 2-speed operation
Control to constant duct pressure (static pressure measurement)
Control to constant volumetric flow for 1 or 2-speed operation
(2 setpoints, dynamic pressure measurement)
Control to constant volumetric flow for 1 or 2-speed operation
(2 setpoints, linear volumetric flow signal measurement)
2. Speed can be switched via time switch (time switch priority
speed 2), room temperature controller or indoor air quality
controller;
speed 2 can be locked at low outside temperatures
Recirculated air operation possible
Configurable precommand output and checkback signal
Settable start delay, separate for supply air and extract air fan
Fan release relay and smoke extraction with fans (see "Faults")
Fans can be directly switched on/off via start and stop conditions
(stop of supply air fan causes plant to stop)
Acquire number of operating hours
Pump / twin pumps
Section 10.2
Configuration Functions
p1 p2
x
xxx
QQQ
2
1
12
V AB
B
dxdd
/
p3
Pump 1
On
Start Stop
Pump A
Pump B
Precommand output ( )
Precommand checkback ( )
Flow signal (
V
)
Overload signal ( )
Start condition 1/2
Stop condition 1/2
Optg mode-dep ON (
/
On
)
Usable as single or twin pump (e.g. heating coil pump) or as main
pump (e.g. chilled water primary controller)
ON via load signal from sequence controller (max 2 sequences
with max selection, settable switching points), ON by operating
mode (operating mode-dependent ON), OT-dependent ON
(settable)
Settable switch-off delay
Settable pump kick
Configurable precommand output and checkback signal
Pump can be directly switched on/off via start and stop conditions
Selectable run priority
Changeover of run priority in automatic operation once a week
(same time as the pump kick)