Basic Documentation

302/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Appendix 03.10.2011
Automatic changeover of run priority in case of fault, settable
changeover time (overlapping or with delay prior to restart of
second pump)
Acquire number of operating hours
Modulating outputs
Section 10.3
Configuration Functions
B
y1 y2 y3
A...D
Modulating output A…D (Y)
Input
Start preset
For continuous signals DC 0…10 V, e.g. for valve control.
Load signal from sequence controller (from max 3 sequences with
maximum selection)
Settable "Positioning signal min" and "Positioning signal max".
Settable inversion
Enable via start input
HR
Section 10.4
Configuration Functions
12 1 2
Y
y1 y2 a
xa a
Q
HR
MECH
CC....................
Output (Y)
MECH input 1
MECH input 2
Efficiency 1
Efficiency 2
Cooling coil valve (modulating,
switching)
To control heat recovery equipment.
Configuration always with "heating" load signal from sequence
controller (from max 2 sequences with max selection)
Maximum economy changeover, optionally with 1 input (digital or
analog) or 2 inputs (differential measurement)
Efficiency supervision with sensor in supply air after HR
equipment or with sensor in exhaust air
HR equipment supports cooling when cooling coil valve opens
(also in case of dehumidification)
Settable "Positioning signal min" and "Positioning signal max"
Settable inversion
Mixed air damper
Section 10.5
Configuration Functions
12
y1 y2
Y
a
x
a
TMil
Damper
MECH
CC.........
Output (Y)
MECH input 1
MECH input 2
Cooling coil valve
Mixed air temperature (TMil)
To control mixed air dampers.
Configuration of sequence controller (from max 2 sequences with
max selection)
Output signal DC 0…10 V (closed / open refer to outside air
damper)
Control mixed air temperature
Maximum economy changeover, optionally with 1 input (digital or
analog) or 2 inputs (differential measurement)
Damper supports cooling when cooling coil valve opens (also in
case of dehumidification)
Selectable start operation
Settable "Positioning signal min" and "Positioning signal max",
max position can be shifted by outside temperature
Step switch
Section 10.6, 10.7
Configuration Functions
123
4
y1 y2
x
QQ Q
Q
Y
y3
Step
switch 1
Linear
Binary
Release
Connect 1+2
Step 1 to ... (Q...)
Modulating output (Y)
Release external
Connect 1+2
To control a multistage aggregate.
Configuration of each step in dependence of load signal from
sequence controller (from max 3 sequences with max selection)
Selection
Linear step switch to switch equal-size steps or aggregates with
equal output for lead/sequential run (run priority changeover)
Binary step switch to switch binary stepped aggregates.
Step switches can be cascaded
Release external of the step switch with digital input, e.g. flow