Basic Documentation

303/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Appendix 03.10.2011
monitoring for electric heating coil
Settable fan overrun time, e.g. for connected electric heating coil
Modulating output can be configured, same function as
"Modulating outputs"
Settable locking time (restart delay) (time applies to all steps)
123456
y1 y2 x
QQQQQQ Y
y3
Step switch 4 (var)
Release
Step 1 to ... (Q...)
Modulating output (Y)
Release external
To control a multistage aggregate.
Depending on the load signal from the sequence controller (max.
3 sequences with maximum selection), each step can be assigned
a switch-on and switch-off point; the switching points may overlap
and can be inverted (ON < OFF)
Release external of the step switch with digital input, e.g. flow
monitoring for electric heating coil
Settable fan overrun time, e.g. for connected electric heating coil
Configurable modulating output
Settable locking time (restart delay) (time applies to all steps)
Logic functions
Section 10.8
Configuration Functions
12 21
xx xx
A
B
3
x
C
Q
d
Logic 1
Input
Logic function
Operation selector
Relay output
Digital output
4 logic blocks, logic 1 to 4
Generation of digital signal from continuous input signals
Selectable logic for logic A, B and C
Selectable operation
Delay times can be set for output signal
Selectable time formats
Heat demand
Section 25
Configuration Functions
S1 S1 S1
S2 S2
x
S2
S3
QY
d
123
Controller
Supervision
Heat demand
Controllers 1 to 3
Supervision
Heat demand modulating
Heat demand relay
Plant functions when heat is requested.
Setting giving the sequences where heating valves are configured
Supervision: When heat is requested, but no heat is available
after a set period of time, a fault message can be triggered, plant
stop can be selected as needed. Digital input or temperature
sensor
Heat demand relay or modulating output to route heat demand
Heat demand can also be transmitted via bus, (see
Communication)
Refrigeration demand
Section 26
Configuration Functions
x
Kältebedarf
QY
d
S4 S4 S4
S5
123
Cooling demand
Supervision
Controller
Controllers 1 to 3
Supervision
Refrig demand modulating
Refrigeration demand relay
Plant functions when refrigeration is requested.
Setting giving the sequences where cooling valves are configured
Supervision: When refrigeration is requested, but no refrigeration
is available after a set period of time, a fault message can be
triggered, plant stop can be selected as needed. Digital input or
temperature sensor
Refrigeration demand relay or modulating output to route
refrigeration demand
Refrigeration demand can also be transmitted via bus, (see
Communication)