Basic Documentation

42/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Operating modes 03.10.2011
Any digital inputs can be assigned to the inputs. For a better overview, we
recommend arranging the inputs side by side.
Misconfiguration has the following effect:
Operating line Value Effect
Room operating mode input 1
Room operating mode input 2
---
N.Xx
No effect
6.5.1 Timer function
The digital input selected for the timer function allows for switching the controller to
Comfort mode (
)
for a selected period of time.
Main menu > Commissioning > Extra configuration > Operating mode >
Operating line Adjustable values / remarks
Timer function ---, N.X1, N.X2, ... (digital inputs only)
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Operating mode >
Operating line Range Factory setting
Timer function 0…720 min 60 min
60 min 60 min 60 min
ON
OFF
A
B
C
3140D05
C
A
ON
OFF
B
3140D06
720 min
A Time switch ( )
B Switching command via digital input for "Timer function" with time set for Comfort mode
C Active operating mode
Recommendation
Misconfiguration
Configuration
Setting values
Function diagrams
Key