Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Operating modes 03.10.2011
For days without entry, the previous day’s operating mode is assumed and
displayed as broken line.
The special day ends with the same operating mode it was started with
The day following the special day assumes the operating mode of the previous
day’s program that would have applied had there been no special day (Tuesday
for the following example)
Cmf
PreCmf
Eco
1
3131D25
Monday Special day Wednesday
After all data is entered for a day, it can be copied to other days. If, for example,
Monday is entered, the same profile can be copied to all the other working days
(Monday through Friday) and need not be entered again.
6.9.3 Release room unit for time switching operating mode
If the individual room controller is equipped with a room unit QAX3x.x (with
operating mode setting or fan speed), it may occur that when specifying room
operating mode Economy using the user time switch, the room unit changes to
Comfort. The result is that the entire air handling unit switches for a single room.
This may further result in unallowed overpressure in the air ducts depending on the
sizing of the air system. The setting parameter "Comfort via room unit" is used to
prevent this.
Comfort via room unit
= Yes
Manual changeover from Economy to Comfort is
possible via QAX3x.x and QAW740
Comfort via room unit
= No
Manual changeover from Economy to Comfort is not
possible via QAX3x.x and QAW740
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Time switch 1 >
Operating line Range Factory Setting
Comfort via room unit Yes / No Yes
6.9.4 Communication
A time switch always operates in the "Geographical zone (apartment)" selected for
the controller. If the controller communicates with other controllers, the 7-day time
switch can be assigned to other controllers. The following settings must be made,
depending on the required operating mode:
Desired operating mode Operating line Setting
Time switch operation
"Autonomous"
Geographical zone (apartm.) Time
switch slave (apartment)
----
----
Time switch operation
"Master"
Geographical zone (apartm.) Time
switch slave (apartment)
1...126
----
Time switch operation
"Slave"
1)
Geographical zone (apartm.) Time
switch slave (apartment)
----
1...126
1)
Slave operation can be selected only in basic types A and U
Setting values