Basic Documentation

53/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Operating modes 03.10.2011
6.10.5 Control input "Holidays / special days"
The holidays and special days can also be activated via digital inputs. To do this,
digital inputs must be assigned.
Main menu > Commissioning > Extra configuration > Operating mode > (A, U)
Main menu > Commissioning > Extra configuration > Time switch 1 > (P and C)
Operating line Adjustable values / remarks
Holiday input ---, N.X1, N.X2, ... (digital inputs only)
Special day input ---, N.X1, N.X2, ... (digital inputs only)
These inputs have an effect only if holidays / special day is set to "Autonomous" or
"Master".
Activation of special day or holidays via digital inputs is not entered in the holidays /
special day program, eliminating recurrence.
The digital input enables the plant to be constantly switched to the special day
program in the 7-day program without requiring interventions on the controller.
If a permanent signal is applied to the configured input, the special day program
becomes active. This program is maintained until there is no more signal. Only
then does the normal 7-day program resume operation.
The digital input enables the plant to be constantly switched to "Holidays" without
requiring intervention on the controller.
If a permanent signal is applied to the configured input, the plant changes to
"Holidays". This operating mode is maintained until there is no more signal. Only
then does the normal 7-day program resume operation.
If a special day or holidays are activated simultaneously via control switches and
entry in the calendar, the following priority list applies:
Control switch "Special day"
Control switch "Holidays"
"Special day" entry in the calendar
"Holidays" entry in the calendar
If other controllers are configured as slaves in the same holidays / special day
zone, the digital inputs also act on these controllers.
6.10.6 Troubleshooting
Only one master may be set per holidays / special day zone. If several controllers
are set as master, a fault status message appears. The fault status signal is sent
by the controller receiving two holidays / special day signals.
If the controller expects a holidays / special day signal from the bus and the signal
is not sent, a fault status message "Holidays / special day program failure"
appears. The operating modes of the 7-day program are used without considering
the holidays / special day entries.
No. Text Effect
5201 Hol/spec day program
failure
Non-urgent message; must not be
acknowledged
5202 >1 hol/spec day
program
Non-urgent message; must be acknowledged
When evaluating the priority in the holidays / special day program, only the first two
entries are considered. If more than two overlapping entries are made, the special
day may no longer have priority over the holidays.
Configuration
Special day
Holidays
Priority
Note
Fault status messages