Basic Documentation

64/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Time switch 2 (ON/OFF) 03.10.2011
After all data is entered for a day, it can be copied to other days. If, for example,
Monday is entered, the same profile can be copied to all the other working days
(Monday through Friday) and need not be entered again.
7.4 Assign texts
Text can be assigned to each time switch and the operation selector. This text
appears on the menu and in the operating line.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Time switch 2 >
Operating line Range Factory setting
Time switch 2 Max. 20 characters Time switch 2
[Time switch 2] op
selector
Max. 20 characters [Time switch 2] op
select
Refer to section 31.4 for an overview of all editable texts and on how to reset them.
7.5 Operation selector
The operating mode of the time switch’s output can be preselected via the
operation selector in the main menu. The current state for the operation selector of
time switch 2, e.g., appears as follows:
Main menu > [[Time switch 2] op selector >
Operating line Range Factory setting
Preselection Auto, Off, On Auto
If the configuration of the operation selector is reset subsequently, you must first
ensure that it is set to Auto. Otherwise, the time switch constantly maintains "On" or
"Off".
Main menu > [[Time switch 2] op selector >
[Time switch 2] op selector
Preselection: Auto
State: Comf
7.6 Troubleshooting
If a time switch signal from the bus is anticipated and not sent, error message
"[Time switch 2] failure" appears. In this case, the receiver continues to operate on
"On".
No. Text Effect
5111 [Time switch 2]
failure
Non-urgent message; must not be acknowledged
Copy 24-hour profiles
Free text
Setting value
Note
Display values
Fault status messages