8.1.2 Cause
The source of the input value is displayed in the value "Cause". The following types
are available:
Terminal: Used as local terminal
LTE mode: Used as LTE transmission and reception objects
S-mode: Used as S-mode object
Simulation: Input terminal simulation
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Operating line Range Factory setting
Cause Terminal, LTE mode, S-
mode, Simulation
The LTE transmission and reception objects are described in Section 28.2.6.
8.1.3 Input terminal simulation
Each input terminal can be simulated to test plant reaction.
Main menu > Inputs > Simulation inputs >
Operating line Range
(depends on type)
Factory setting
(by type)
N.X1…
A8 (2).X4
----, 50... 50 °C
----
The inputs should only be overridden by qualified staff and within a limited period of
time!
The fault message "Simulation inputs active" is sent during terminal simulation.
No. Text Effect
100 Simulation inputs active Non urgent message; must not be
acknowledged.
The fault message remains active until "Simulation " is reset to "----". This is to
make certain it will not be forgotten on the plant to reset the simulation.
The simulated input terminal value is used only locally. It is not sent via bus to other
controllers.
Note
Setting values
Fault status messages
Note