8.2 Analog inputs
Analog inputs can be activated as described in section 8.1.1 "Activate function".
With the analog inputs, the following settings are available:
Type, measuring range and readjustment.
8.2.1 Type
If the unit is °C, the type can be selected. If the unit is not °C, the type is always
0...10 V.
The following types are available:
LG-Ni1000
2xLG-Ni1000
T1
Pt1000
0...10 V
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Operating
line
Range Factory setting
Type Ni1000, 2xNi1000, T1, Pt1000, 0…10
V
Ni1000
8.2.2 Measuring range
Passive temperature signals from LG-Ni 1000 sensing elements have a measuring
range of 50…250 °C.
Passive temperature signals from 2x LG-Ni 1000 or T1 sensing elements have a
measuring range of 50...150 °C.
Passive temperature signals from Pt1000 sensing elements have a measuring
range of 50...+ 400 °C.
With active signals, the measuring range is definable. A lower and an upper
measured value must be entered.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Operating
line
Range Factory setting
Value low Depending on selected type Depending on type
Value high Depending on selected type Depending on type
Room temperature with an active signal of DC 0...10 V = 0...50 °C:
Lower measured value: 0 °C
Upper measured value: 50 °C
Setting values
Setting values
Example