8.2.3 Measured value correction
With passive temperature sensors, the measured value can be readjusted by 3.0
to 3.0 K to compensate for line resistance. It is thus possible to on-site calibrate
using a reference instrument.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Operating line Range Factory setting
Correction
3.0…3.0 K
0 K
8.2.4 Connection examples for sensors
Temperature measurement with passive temperature sensor using LG-Ni 1000
sensing element.
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line Setting
N.X1 °C
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Operating line Setting
Type Ni1000
G
G
G0
X...
M
G0
B...
N
3123A06
AC 24 V
BM
LG-Ni 1000
Average temperature measurement with 2 passive sensors using LG-Ni 1000
sensing elements.
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line Setting
N.X1 °C
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Operating line Setting
Type 2xNi1000
Setting values
Example 1
Input configuration
Setting values
Connection diagram
Example 2
Input configuration
Setting values