8.2.6 Multiple use of sensors
Not all sensor signals can be routed via bus to another device. For this reason,
function "Multiple use of sensors" allows for wiring a passive signal at an input
terminal directly to a Y-output and provide it as a DC 0…10 V signal. The signal
can then be fed to other devices.
Main menu > Commissioning > Extra configuration > Sensor multiple use
Operating line Adjustable values / remarks
Signal Y N.X1, … Activate function by assigning an input terminal to the
output terminal
Converting signal LG-Ni1000 or Pt1000 to signal DC 0...10 V is carried out by
setting parameters "Value low" and "Value high".
Input terminal simulation is not available for multiple use of sensors.