8.4 Outside temperature
8.4.1 Possible connections
The outside temperature can be provided by different sources:
Outside temperature connected locally to terminal
Outside temperature via bus
The following variants are available:
Variant Effect Diagram
Outside temperature
at the terminal.
Communication
outside temperature
not active.
Controller operates with own
outside temperature, no
impact on the bus
T
Outside temperature
at the terminal.
Communication
outside temperature
active.
Controller operates with own
outside temperature. Using
the bus, the outside
temperature is also provided
to other controllers
T
No outside
temperature at
terminal.
Communication
outside temperature
active.
Controller operates with
outside temperature provided
via bus by another controller
3123Z06
T
No outside
temperature at
terminal.
Communication
outside temperature
not active.
Controller has no outside
temperature
T
8.4.2 Outside temperature at terminal
Refer to section 8.2 "Analog inputs" for settings and connection diagram for outside
temperature at the terminal.
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line Adjustable values / remarks
…X… Activate function by assigning the "Outside
temperature" value to the input
8.4.3 Outside temperature via bus
The outside temperature can only be provided via the bus if communication is
active and an outside temperature set (Outside temperature zone = "----" means
that the outside temperature on the bus is inactive).
To activate different outside temperatures to be sent via bus (e.g. outside
temperature on the northern side of the building for the air conditioning plants, and
outside temperature on the eastern side of the building for heating zone "East",
etc.), they must be assigned to specific outside temperature zones.
Refer to section 28 "Communication" for the required settings.
Config
uration