Basic Documentation

75/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Inputs 03.10.2011
Main menu > Commissioning > Communication > Distribution zones >
Operating line Range Factory setting
Outside temperature
zone
----, 1…31 ----
8.4.4 Outside temperature simulation
To simulate the outside temperature and test the response of the plant, the
measured value of the outside temperature can be overridden.
Main menu > Inputs >
Operating line Range Factory setting
Outside temperature
simulation
----, 50... 50 °C
----
Only authorized staff may override inputs within a limited period of time!
During simulation of the outside temperature, message "Outs sensor simulation
active" appears.
No. Text Effect
12 Outs sensor
simulation active
Non-urgent message; must not be
acknowledged
This message remains active until "Simulation " is returned to "----". This ensures
that the simulation is always completed.
The simulated outside temperature is used only locally; it is not sent via bus to
other controllers.
8.4.5 Troubleshooting
When you exit the "Commissioning" menu, a check is carried out to see if the
outside temperature is connected. If the outside temperature is connected at this
point and missing later, message "[...X...] sensor error" appears.
For each system, only one outside temperature can be sent within the same zone
(only one outside temperature master).
If several controllers send outside temperatures within the same zone, message
">1 outside temperature sensor" appears. The fault is sent by the controllers
sending and receiving outside temperature signals to and from the same zone.
If the controller expects an outside temperature signal via the bus and the signal is
not sent, message "Outside temperature sensor fault" appears.
No. Text Effect
101…
[N.X1] sensor error Non-urgent message; must not be
acknowledged
11 >1 outside
temperature sensor
Urgent message; must be acknowledged
10 Outside temp
sensor error
Non-urgent message; must not be
acknowledged
If other outside temperature signals are available on the bus, any of them are used
randomly.
Setting values
Setting values
Fault status messages
Note
Fault status messages