8.8.4 Connection diagram
Connect the setpoint adjuster according to the following diagram:
G
BM MBMB2
G
G0
X... M MX... MX...
G0
B1 B5 R5
N1
3144A01
AC 24 V
(1)(3)
R5 Passive setpoint shifting unit BSG21.5
8.8.5 Troubleshooting
Error in operation
When you exit the Commissioning menu, a check is made to see if the setpoint
adjuster is connected.
If the setpoint adjuster is connected at this point but missing later, message "[...X...]
sensor error" appears.
No. Text Effect
101…
[N.X1] sensor error Non-urgent message; must not be
acknowledged
If there is no signal from the setpoint adjuster, the controller continues to work
without relative setpoint shift.
Configuration error
If more than one input is activated as remote setpoint adjuster, only the first is
considered.
Fault status messages