Basic Documentation

84/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Inputs 03.10.2011
8.9 Pulse
An input with this identifier can be used to connect a pulse counter. Pulses with the
following specification can be received:
Mechanical sources (Reed contact) without Namur circuitry, max. pulse
frequency of 25 Hz and a min. pulse duration of 20 ms
Electronic pulse source with max. pulse frequency of 100 Hz and min. pulse
duration of 5 ms
8.9.1 Activate function
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line Adjustable values / remarks
…X… Pulse
Electronic pulse sources (e.g. Open Collector outputs) generate shorter, less
bouncing pulses than mechanical pulse sources (e.g. relays or Reed contacts).
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Operating line Range Factory setting
Type Mechanical or Electronic Mechanical
8.9.2 Connection diagram
G
G
G0
X... M
G0
R1
N
3123A10
AC 24 V
+/-+/-
R1 Reed pulse source
8.10 Assign texts
For every input, the texts can be adjusted via operation.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Operating line Range Factory setting
N.Xx Max. 20 characters N.Xx
Refer to section 31.4 for an overview of all editable texts and on how to reset them.