User Manual
Building Technologies / HVAC Products CE1G2725en 23.03.2005 1/4
G2725
en
Installation and commissioning guide
Temperature controller
RRV851
Installation
Place of installation
• Mounting choices:
− Control cabinet
− Control panel
− Side of FCU
− Wall, ceiling space, cupboard
• Easy access is required for service personnel
• The controller should not be freely accessible by build-
ing occupants
• Do not install outside without suitable weather protection
• Permissible ambient temperature: 0..50°C
Electrical installation
• The local regulations for electrical installations must be
observed
• Cable restraints must be used for the wires to terminals
L,N,Q.. (AC230V)
• Cable restraints should be used for all wiring to avoid
disconnection (see diagram below)
80160
Permissible cable lengths
• For all field devices: room unit, sensors
− max. 60 m where A ≥ 0.5 mm
2
− max. 100 m where A ≥ 1.0 mm
2
• Signal cable type
− 2-wire standard installation cable (unshielded)
− Twisted pair (unshielded) is recom-
mended for enhanced immunity to external electro-
magnetic interference, for example, in the vicinity of
radio transmitters or frequency converters.
• RRV851 controller can be mounted in any orientation
• Ensure adequate air circulation to dissipate heat gener-
ated during operation
DIN rail mounting
1. The housing rail is designed for snap mounting on DIN
rails, type EN50022-35 X 7.5
Surface mounting
1. Hold controller against the surface
2. Mark fixing holes on the wall
3. Drill holes
4. Screw controller to the surface
5. When mounting controller to a FCU, take care not to
damage internal components. E.g. Drilling through
coils
Terminal covers
• The covers will provide IP30 protection when surface
mounting on wall or FCU. IP20 without terminal covers
• The terminal covers include screws for fixing to control-
ler and knock-out holes for cable entry