Operating Instructions – Heating Controllers RVL479, RVL480, RVL481, RVL482 Content Overview, display, and symbols ..................................................... 4 Info button....................................................................................... 7 Operating modes ............................................................................ 8 Switching the heating ON ............................................................... 9 D.h.w. heating........................................
2 2540Z05 1 3 4 5 7 6 A B C 11 8 Siemens Building Technologies 9 10 CE1B2540en 74 319 0616 0 b 18.07.
Overview – what is where? 1 Operating mode buttons. The button indicating the current operating mode is lit 2 Button for d.h.w.
Meaning of symbols on the display NORMAL heating REDUCED heating ECO No heating required according to the prevailing outdoor temperature Holiday mode Heating OFF (frost protection ensured) Solar d.h.w. charging (only RVL481, RVL482) Fault in the plant One of the maximum limitations is active One of the minimum limitations is active BUS Controller connected to the data bus Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.
You want to obtain information Press several times to display the: Time of day Outdoor temperature Room temperature (only if a sensor is used) Flow or boiler temperature The marking indicates the displayed variable. The info selected last is permanently displayed! Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.
The different operating modes Heating OFF Automatic heating up and setback according to the heating program / Heating automatically OFF during the holiday period entered / Heating automatically OFF if permitted by the prevailing outdoor temperature (ECO function) Continuously REDUCED heating Continuously NORMAL heating Frost protection ensured in all operating modes Remote operation with a room unit is only possible in AUTO mode.
You want to switch the heating ON • Is the heating plant ready to operate? Check position of the mains isolator button several times until the display shows the weekday and the time of day. Make corrections, if necessary • Check date and time. Make corrections, if necessary • Press for AUTO mode • Activate the d.h.w.
You want d.h.w. heating (Only RVL481, RVL482) Press to switch d.h.w. heating ON (button lit) and OFF (button extinguished). When the button is lit, the controller provides d.h.w. heating at the following times, depending on the settings made by your heating engineer: According to switching program 2 According to the heating program 24 hours per day (⌧ Mark with a cross whichever applies) Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.
For plants with d.h.w. storage tank, press until the button flashes to charge it manually (not possible in plants where d.h.w. is heated electrically). The d.h.w. is heated with a solar collector provided that your plant is equipped accordingly. The symbol indicates that solar d.h.w. is heated. D.h.w. heating is independent of the controller's operating mode. During the holiday period, d.h.w. is not heated. Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.
Room temperature is not correct • Room temperature too low: 2540Z07 If the room temperature is never correct, neither in mild nor in cold weather, make a room temperature readjustment with the setting knob: Turn the knob toward + • Room temperature too high: Turn the knob toward – The setting knob's scale gives the room temperature readjustment in °C. If the room temperature is not correct in mild weather only or in cold weather only, make the readjustment with the heating curve.
Setting choice Analog Room temperature not correct in mild weather Use slider on the left and readjust by about 5 °C Room temperature not correct in cold weather Use slider on the right and readjust by about 5 °C Digital Readjust line by Readjust line by about 5 °C about 5 °C Via data Contact plant operator Contact plant operabus tor (⌧ Mark with a cross whichever applies) After having made a readjustment, wait two days – the room temperature requires a certain time to adapt! Siemens Building Technolog
You don't want to heat according to the heating program • No setback: Press to select NORMAL mode • Reduced heating: Press to select REDUCED mode Don't forget to return to the normal heating program! The controller operates according to the heating program only when in AUTO mode. Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.
How to query or readjust setting values • Press or to access the setting level • The settings are assigned to several lines: Select next line below Select next line above • Readjustment of values: Decrease Increase • The value is adopted by selecting the next line or by leaving the setting level • Leaving the setting level: Press button of the required operating mode, or the info button, or automatically after 30 minutes For list of lines, refer to the last page of these instructions.
You want to select other room temperature setpoints To select lines: Press and To readjust values: Press and • On line , change the setpoint of NORMAL heating (display ). Standard setting: 20 °C • On line , change the setting of REDUCED heating (display ). Standard setting: 14 °C • On line , change the setpoint of protection and holiday mode (display ). Standard setting: 10 °C To leave the setting level: Select the required operating mode.
You want to change the heating program To select lines: Press and To readjust values: Press and 2541Z04 For the daily heating up and setback, the controller comes with the following standard heating program: • Daily from 06:00 to 22:00: NORMAL heating • Daily from 22:00 to 06:00: REDUCED heating You can enter a maximum of three heating periods per day.
Procedure: 1. On line , select the weekday whose times you want to change: 1 = Monday, 2 = Tuesday, etc. 1-7 = all weekdays 2. On line , set the time for the start of NORMAL heating. 3. On line , set the time for the end of NORMAL heating. If additional daily heating periods are required: and , set the times required for the start 4. On lines and the end of the 2nd heating period. 5. On lines and , set the times required for the start and the end of the 3rd heating period.
2541Z05 Example of a 24-hour program with three heating periods: NORMAL heating from 07:00 to 12:00, from 14:00 to 18:00, and from 19:00 to 23:00 If the settings for the weekend differ from the other weekdays, first enter the times for the entire week (1-7); then, change weekdays 6 and 7. Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.
You want to enter your holidays To select lines: Press and To readjust values: Press and The data for a maximum of eight holiday periods can be entered. To enter the data for one period, proceed as follows: 1. Line : Enter the number of the holiday period. : Enter the date of the first day. 2. Line 3. Line : Enter the date of the last day (possible only when an entry on line has been made). until --.-- appears on the To cancel an entry, change line display.
You want to query the d.h.w. temperature or readjust the d.h.w. setpoint (Only RVL481, RVL482) To select lines: Press and To readjust values: Press and • Set the NORMAL d.h.w. temperature setpoint on line . The standard setting is 55 °C • Query the current d.h.w. temperature on line • Set the REDUCED d.h.w. temperature setpoint on line . This setpoint is used during the OFF periods of the selected program. The standard setting is 40 °C To leave the setting level: Select the required operating mode.
You want to change switching program 2 (Only RVL481, RVL482) In addition to the switching program for the heating periods, the controller has a second switching program. In your plant, your heating engineer has assigned it to .............................................................................. The factory settings are as follows: • Daily from 05:00 to 22:00: ON • Daily from 22:00 to 05:00: OFF Each day can accommodate a maximum of three ON periods.
To select lines: Press and To readjust values: Press and 1. On line , select the weekday whose times you want to change: 1 = Monday, 2 = Tuesday, etc. 1-7 = all weekdays 2. On lines and , set the times required for the start and the end of the 1st ON period. 3. On lines and , set the times required for the start and the end of the 2nd ON period. 4. On lines and , set the times required for the start and the end of the 3rd ON period. To cancel an ON period, change line , or until --:-- appears.
You want to set the clock To select lines: Press and To readjust values: Press and 1. To set the time of day: select line 2. The weekday on line (1 = Monday, 2 = Tuesday, etc.) is set automatically with the date 3. Use the same procedure just as for the time of day: • the date (day and month) on line • the year on line To leave the setting level: Select the required operating mode. The change from wintertime to summertime, and vice versa, is made automatically.
Savings tips without sacrificing comfort • During the day, make certain that room temperatures • • • • • • of 21 °C will not be exceeded. Every degree above that level will increase heating costs by 6 to 7 % Renew the air in the house quickly, with windows fully open Set the thermostatic radiator valves in unoccupied rooms to their frost protection position Radiators should not be covered by curtains, furniture, etc., as these reduce heat emissions Closed window shutters, blinds, etc.
Tips to follow if something seems wrong • The heating does not work: − Check the display. If ECO (economy) is shown, no heating is currently required due to high outdoor temperatures! • The heating always maintains the same room temperature: − Check the operating mode used (only AUTO mode provides setback and heats up again) • The control has a room unit, but it cannot be operated: − Check controller's operating mode.
Faults and manual operation If you are uncertain: − Is the plant switched ON? − Are all plant fuses in order? − Is sufficient fuel in the tank? − Has the controller been readjusted by unauthorized persons? (Time of day, setpoints, etc.) − Check the display.
52 = fault storage tank temperature sensor/control thermostat 2 54 = fault d.h.w. flow temperature sensor 60 = fault room temperature sensor 61 = fault room unit 62 = wrong room unit connected 73 = fault collector sensor 81 = short-circuit on the bus 82 = same bus address assigned several times 100 = two clock masters on the bus 120 = flow alarm 140 = inadmissible bus address or plant type 142 = no partner unit on the data bus These error codes are very useful for service staff.
If the controller uses a room temperature sensor (room unit): − Is the sensor affected by drafts, direct solar radiation, etc.? − Is the sensor affected by heat gains, such as people, machines, lighting, etc.? − Is the sensor covered by furniture, curtains, etc.
the second stage can be switched ON and OFF by pressing button C. In the case of modulating burners, modulation can be changed by pressing button B (OPEN) or C (CLOSE) (only with RVL482) − D.h.w. heating (only with RVL481, RVL482): The pumps used for d.h.w. heating run continuously. If the d.h.w. plant uses a mixing valve, you can drive it manually to the required position. In plants with a changeover valve, d.h.w. heating is not possible.
− The coupling mechanism between actuator and valve is disengaged: Engage it! If you cannot correct the problem, call in your heating engineer. Address and phone no. of your heating engineer: Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.
Setpoint of NORMAL heating Setpoint of REDUCED heating Setpoint of holiday period / protection mode Weekday (1 to 7), for entering the heating program to Entry of heating phases for the heating program Number of the holiday period (1 to 8) First day of the holiday period (day.month) Last day of the holiday period (day.month) Heating curve, flow temperature at +15 °C Heating curve, flow temperature at –5 °C NORMAL d.h.w. temperature setpoint Actual value of the d.h.w. temperature REDUCED d.h.w.