Siemens Basic Documentation RVP340, RVP350, RVP351 CE1P2545en
Building Technologies 21 Handling 15.03.2011
Basic information about the plant is obtained by pressing and .
Meaning:
Number Plant information
--- Time of day
0 Outside temperature B9
1 Flow temperature
2 Room temperature
3 Return temperature
4* D.h.w. temperature B31
5* D.h.w. temperature B32
6* Collector temperature B6
7* Boiler temperature B2
* Not available with RVP340
The information selected last is continuously displayed.
21.1.3 Setting levels and access rights
The operating lines are assigned to different levels. Assignment and access are as
follows:
Level Op. lines Access
Enduser 1 to 50
Press
or
Heating
engineer
51 to 208
Press
and simultaneously for 3 seconds
Locking level 248
Press
and simultaneously until ap-
pears; then, press
, , and , one after
the other
The end-user can access all analog operating elements. This means that he
can select the operating mode, readjust the room temperature with the knob,
and activate manual control. Also, he is allowed to access operating lines 1
through 50
The heating engineer can access all operating elements and all operating lines
Info values
Setting levels
Access rights