User Manual

Siemens Building Technologies Application : 78 RWD32/78 – 04.2001
HVAC Products RWD32 1
RWD32/78
RWD32 Universal Controller
Application 78
Maximum priority
Room temperature control
Chilled water control valve- 3
p
os
230Vac control system
Control ( P or PI )
Room temperature control
Proportional control of the 3 position chilled water valve.
Maximum priority function to control the cooling valve.
Optional day / night set point adjustment .
S1
X1
X2
D1
Q1
Q2
CP
........RWD32.......
M1
CCV
RWD82/75
X1
X2
S1
Q1
Q2
CCV
N1-3
PC
Room temperature sensor
Input from other controllers
Time clock or switch
Opening output for CCV
Closing output for CCV
3 - position chilled water control valve
Temperature controllers.
Personal computer
X1
Universal analogue input - main sensor
Auxiliary analogue input
Digital input
Digital output
Digital output
Communication port
T
X2
N1
N2
N3
X2
X2
Y2
Y2
Y2
Room temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
Adjustable proportional band of 3-position output Q1, Q2.
Integral action function selection and adjustment.
Timing of 3-position valve actuator
230Vac controller supply voltage
230Vac three position control valves
The cooling coil control valve is controlled by the highest call for cooling from a
number of zones via the priority function in the temperature controller
Day / night set points can be selected via time clock or switch.
Supplemental features
Control
Operating modes

Summary of content (3 pages)