User Manual
Siemens Building Technologies Application :30 RWD62/30 - 02.2001
HVAC Products RWD62 1
RWD62/30
RWD62 Universal Controller
Application 30
Room temperature control
Hot water control valve
Chilled water control valve
Control (P or PI)
Room temperature control
Proportional control ( 0..10Vdc ) of the hot water valve.
Proportional control ( 0..10Vdc ) of the chilled water valve.
Optional day / night set point adjustment .
S1
X1
X2
D1
Y1
Y2
CP
........RWD62.......
M1
Y1
RWD62/30
X1
S1
Y1
Y2
PC
Room temperature sensor
Time clock or switch
modulating hot water valve
modulating chilled water valve.
Personal computer
X1
Universal analogue input - main sensor
Auxiliary analogue input
Digital input
Analogue output
Analogue output
Communication port
T
Y2
• Room temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
• Adjustable dead zone with separate heating and cooling set points.
• Adjustable proportional band of analogue output Y1.
• Adjustable proportional band of analogue output Y2.
• Adjustable Integral action function selection and adjustment for Y1 & Y2.
• Day / night set points can be selected via time clock or switch.
Supplemental features
Control
Operating modes