User Manual

Siemens Building Technologies Application :15 RWD62/15 - 05.2001
HVAC Products RWD62 1
RWD62/15
RWD62 Universal Controller
Application 15
Cascade control
Room temperature control
Hot water control valve
Control (P or PI)
Room temperature control
Proportional control ( 0..10Vdc ) of the hot water valve.
Cascade control.
Optional day / night set point adjustment .
S1
X1
X2
D1
Y1
Y2
CP
........RWD62.......
M1
Y1
RWD62/15
X1
X2
S1
Y1
PC
Room temperature sensor
Supply air temperature sensor
Time clock or switch
Modulating hot water valve
Personal computer
X1
Universal analogue input - main sensor
Auxiliary analogue input
Digital input
Analogue output
Analogue output
Communication port
T
T
X2
Room temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
Adjustable proportional band of analogue output Y1.
Adjustable Integral action function selection and adjustment for Y1.
Duct temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
Cascade control of the supply air by the room temperature sensor.
Day / night set points can be selected via time clock or switch.
Supplemental features
Control
Operating modes