User Manual

Siemens Building Technologies Application :15 RWD62/15 - 05.2001
HVAC Products RWD62 2
The temperature sensor senses the room conditions and on a fall in temperature
the RWD62 via Y1 analogue output modulates the hot water valve as determined
by the heating set point and proportional band (XP) setting.
Cascade control is where deviation of room temperature from set point adjusts
the control point of the leaving air temperature sensor controlling cooling
Heating sequence
Y1
Min V
Heating Setpoint
Ouptut
Voltage
Max V
Load
Heating
XP
Y1
G
Y1
S1
D1
GO
Y..
BM
X1 X2MM
RWD62/3
0
X1
M
M
GO
G
24 V SN
24 V SP
N1
TOOL
PC
G
M
Y2
B
M
G
X2
RWD62
N1 RWD62 controller
X1 Main temperature sensor
X2 Supply air temperature sensor
S1 Time clock or switch
Y1 Heating control valve with 0..10Vdc input
PC Personal computer
Description of operation
Function diagram
Connection diagram