User Manual

Siemens Building Technologies Phoenix Application :52 RWD62/52 - 05.2001
HVAC Products RWD62
3
The main display shows ,
a) Y1 output in Volts dc. (0..10V = 0..100% range)
b) Y2 output in Volts dc. (0..10V = 0..100% range)
c) Whether day or night set point is selected. ( ¤ = day, b = night)
d) X1 value ( room temperature) in ° C.
.
Other displays are available by pressing the + button, and the various
displays are listed below in sequence from the main display.
On entering any of the four set point displays, the setpoint on display can be
adjusted by pushing the enter/save button, increase value by pressing the
+ button or decrease the value by pressing the – button, and when the
required value is reached, press the enter/save button to save the new
value.
The alternative displays return to the main display after 20 seconds.
Press
buttons
Action Current display Selected display Selected display comments.
Push + button
Y1 Y2 ¤ X1 SP – c ¤ 25.0c cooling day set point.
Push + button
SP – c ¤ 25.0c SP – c b 32.0c cooling night set point
Push + button SP – c b 32.0c X1 22.0c X1 - main temperature sensor reading
Push + button X1 22.0c X2 19.0c X2 - limit temperature sensor reading
Push + button X2 19.0c Y1 5.0 Y1 – cooling analogue output value in Vdc to one decimal point
Push + button Y1 5.0 Y2 0.0 Y2 – cooling analogue output value in Vdc to one decimal point.
Push + button Y2 0.0 LIM 52
ABS
Control sequence diagram and application number display.
Push + button LIM 52
ABS
Y1 Y2 ¤ X1 Back to main display.
Values shown are either default values or nominated for information only
Main Display