User Manual

Siemens Building Technologies Application :37 RWD62/37 - 05.2001
HVAC Products RWD62 1
RWD62/36
RWD62 Universal Controller
Application 36
W / S mode selection - analogue
Room temperature control
Hot water control valve
Chilled water control valve
Control (P or PI)
Room temperature control
Proportional control ( 0..10Vdc ) of the hot water valve.
Proportional control ( 0..10Vdc ) of the chilled water valve.
Winter/Summer selection of heating or cooling operation of Y1 via analogue input
Optional day / night set point adjustment .
S1
X1
X2
D1
Y1
Y2
CP
........RWD62.......
M1
Y1
RWD62/37
X1
X2
S1
Y1
Y2
PC
Room temperature sensor
Outside air temperature sensor
Time clock or switch
Modulating hot / chilled water valve
Modulating chilled water valve.
Personal computer
X1
Universal analogue input - main sensor
Auxiliary analogue input
Digital input
Analogue output
Analogue output
Communication port
T
Y2
T
Room temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
Adjustable dead zone with separate heating and cooling set points.
Adjustable proportional band of analogue output Y1.
Adjustable proportional band of analogue output Y2.
Adjustable Integral action function selection and adjustment.
Duct temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
Outside air temperature sensor provides the analogue input for winter / summer
selection.
Day / night set points can be selected via time clock or switch.
Winter / summer selection of heating and cooling mode of the Y1 output as selected
by analogue input into auxiliary input X2 sensing outside air temperature.
The water supplied to the coil must be changed from heating water to chilled water
and interlocked with the winter / summer change over function
Supplemental features
Control
Operating modes