User Manual

Siemens Building Technologies Application :68 RWD68/68 - 02.2001
HVAC Products RWD68 1
RWD68/68
RWD68 Universal Controller
Application 68
Maximum priority
Room temperature control
Chilled water control valve
Chilled water pump output
Control (P or PI)
Room temperature control
Proportional control ( 0..10Vdc ) of the chilled water valve.
Digital output to energise chilled water pump ( dependent )
Maximum priority function to control the cooling valve.
Optional day / night set point adjustment .
S1
X1
X2
D1
Y1
Q1
CP
........RWD68.......
M1
Y1
RWD68/68
X1
X2
S1
Y1
Q1
PC
Room temperature sensor
Input from other controllers
Time clock or switch
2-port chilled water valve
Chilled water pump
Personal computer
X1
Universal analogue input - main sensor
Auxiliary analogue input
Digital input
Analogue output
Digital output
Communication port
T
Q1
0..10Vdc cooling outputs
other controllers
Room temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
Adjustable differential of digital output Q1.
Adjustable proportional band of analogue output Y1.
Integral action function selection and adjustment for output Y1.
24Vac controller supply voltage
0..10Vdc modulating control valve
The cooling coil control valve is controlled by the highest call for cooling from other
zones via the final temperature controller and the maximum priority function in this
temperature controller.
Day / night set points can be selected via time clock or switch.
Dependent mode for the two cooling outputs, meaning that the digital output on and
off settings are set within the analogue output proportional band.