User Manual
Siemens Building Technologies Application :68 RWD68/68 - 02.2001
HVAC Products RWD68 1
RWD68/68
RWD68 Universal Controller
Application 68
Maximum priority
Room temperature control
Chilled water control valve
Chilled water pump output
Control (P or PI)
Room temperature control
Proportional control ( 0..10Vdc ) of the chilled water valve.
Digital output to energise chilled water pump ( dependent )
Maximum priority function to control the cooling valve.
Optional day / night set point adjustment .
S1
X1
X2
D1
Y1
Q1
CP
........RWD68.......
M1
Y1
RWD68/68
X1
X2
S1
Y1
Q1
PC
Room temperature sensor
Input from other controllers
Time clock or switch
2-port chilled water valve
Chilled water pump
Personal computer
X1
Universal analogue input - main sensor
Auxiliary analogue input
Digital input
Analogue output
Digital output
Communication port
T
Q1
0..10Vdc cooling outputs
other controllers
• Room temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
• Adjustable differential of digital output Q1.
• Adjustable proportional band of analogue output Y1.
• Integral action function selection and adjustment for output Y1.
• 24Vac controller supply voltage
• 0..10Vdc modulating control valve
• The cooling coil control valve is controlled by the highest call for cooling from other
zones via the final temperature controller and the maximum priority function in this
temperature controller.
• Day / night set points can be selected via time clock or switch.
• Dependent mode for the two cooling outputs, meaning that the digital output on and
off settings are set within the analogue output proportional band.
Supplemental features
Control
Operating modes