User Manual

Siemens Building Technologies Application :74 RWD68/74 - 02.2001
HVAC Products RWD68 1
RWD68/74
RWD68 Universal Controller
Application 74
Compensation shift
Room temperature control
Chilled water control valve
Two speed fan
Control (P or PI)
Room temperature control
Proportional control ( 0..10Vdc ) of the chilled water valve.
Digital output to energise second stage of supply fan
Outside air compensation of the supply air temperature set point.
Optional day / night set point adjustment .
S1
X1
X2
D1
Y1
Q1
CP
........RWD68.......
M1
Y1
RWD68/73
X1
X2
S1
Y1
Q1
PC
Room temperature sensor
Outside air temperature sensor.
Time clock or switch
2-port chilled water valve
Fan speed contactor.
Personal computer
X1
Universal analogue input - main sensor
Auxiliary analogue input
Digital input
Analogue output
Digital output
Communication port
Q1
100%50%
T
X2
T
Room temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
Adjustable differential of digital output Q1.
Adjustable proportional band of analogue output Y1.
Integral action function selection and adjustment for output Y1.
24Vac controller supply voltage
0..10Vdc modulating control valve
Outside air temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
Outside air compensation of the supply air temperature set point.
Day / night set points can be selected via time clock or switch.
Independent mode for the two cooling outputs, meaning that the digital output on and
off settings are set outside the analogue output proportional band.