User Manual
Siemens Building Technologies Application :74 RWD68/74 - 02.2001
HVAC Products RWD68 1
RWD68/74
RWD68 Universal Controller
Application 74
Compensation shift
Room temperature control
Chilled water control valve
Two speed fan
Control (P or PI)
Room temperature control
Proportional control ( 0..10Vdc ) of the chilled water valve.
Digital output to energise second stage of supply fan
Outside air compensation of the supply air temperature set point.
Optional day / night set point adjustment .
S1
X1
X2
D1
Y1
Q1
CP
........RWD68.......
M1
Y1
RWD68/73
X1
X2
S1
Y1
Q1
PC
Room temperature sensor
Outside air temperature sensor.
Time clock or switch
2-port chilled water valve
Fan speed contactor.
Personal computer
X1
Universal analogue input - main sensor
Auxiliary analogue input
Digital input
Analogue output
Digital output
Communication port
Q1
100%50%
T
X2
T
• Room temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
• Adjustable differential of digital output Q1.
• Adjustable proportional band of analogue output Y1.
• Integral action function selection and adjustment for output Y1.
• 24Vac controller supply voltage
• 0..10Vdc modulating control valve
• Outside air temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
• Outside air compensation of the supply air temperature set point.
• Day / night set points can be selected via time clock or switch.
• Independent mode for the two cooling outputs, meaning that the digital output on and
off settings are set outside the analogue output proportional band.
Supplemental features
Control
Operating modes