User Manual

Siemens Building Technologies Application :46 RWD82/46 - 02.2001
HVAC Products RWD82 1
RWD82/46
RWD82 Universal Controller
Application 46
W / S mode selection - digital
Room temperature control
Hot water control valve
Chilled water control valve
Control ( 2 position )
Room temperature control
2 position control of the hot water control valve
2 position control of the chilled water control valve
Winter / Summer selection of heating or cooling operation of Q1 output by X2
Optional day / night set point adjustment .
S1
X1
X2
D1
Q1
Q2
CP
........RWD82.......
M1
Q1
RWD32/46
X1
X2
S1
Q1
Q2
PC
Room temperature sensor
Outside air thermostat
Time clock or switch
2-position hot / chilled water valve
2-position chilled water valve.
Personal computer
X1
Universal analogue input - main sensor
Auxiliary analogue input
Digital input
Digital output
Digital output
Communication port
T
Q2
X2
T
Room temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
Adjustable dead zone with separate heating and cooling set points.
Adjustable differential of digital output Q1.
Adjustable differential of digital output Q2.
24Vac controller supply voltage
24Vac two position control valves
Outdoor air temperature sensor can be selected as Ni1000, Pt1000, or active
sensor.(X2)
Winter / summer selection of heating or cooling mode of the Q1 output as selected by
digital input into auxiliary input X2 sensing outside air temperature.
Day / night set points can be selected via time clock or switch.
Supplemental features
Control
Operating modes