User Manual

Siemens Building Technologies Application :40 RWD82/40 - 02.2001
HVAC Products RWD82 1
RWD82/40
RWD82 Universal Controller
Application 40
Room temperature control
Hot water control valve
Chilled water control valve
Control ( 2 position )
Room temperature control
2 position control of the hot water control valve
2 position control of the chilled water control valve
Optional day / night set point adjustment .
S1
X1
X2
D1
Q1
Q2
CP
........RWD82.......
M1
Q1
RWD82/40
X1
S1
Q1
Q2
PC
Room temperature sensor
Time clock or switch
2-position hot water valve
2-position chilled water valve.
Personal computer
X1
Universal analogue input - main sensor
Auxiliary analogue input
Digital input
Digital output
Digital output
Communication port
T
Q2
Room temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
Adjustable dead zone with separate heating and cooling set points.
Adjustable differential of digital output Q1.
Adjustable differential of digital output Q2.
24Vac controller supply voltage
24Vac two position control valves
Day / night set points can be selected via time clock or switch.
Supplemental features
Control
Operating modes

Summary of content (3 pages)