User Manual
Siemens Building Technologies Application :41 RWD82/41 - 02.2001
HVAC Products RWD82 1
RWD82/41
RWD82 Universal Controller
Application 41
Remote set point
Room temperature control
Hot water control valve
Chilled water control valve
Control 2 stage on / off ( 2 position )
Room temperature control
2 position control of the hot water control valve
2 position control of the chilled water control valve
Remote set point adjustment
Optional day / night set point adjustment .
S1
X1
X2
D1
Q1
Q2
CP
........RWD82.......
M1
Q1
RWD82/41
X1
X2
S1
Q1
Q2
PC
Room temperature sensor
Remote setpoint adjuster
Time clock or switch
2-position hot water valve
2-position chilled water valve.
Personal computer
X1
Universal analogue input - main sensor
Auxiliary analogue input
Digital input
Digital output
Digital output
Communication port
T
Q2
R
• Room temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
• Adjustable dead zone with separate heating and cooling set points.
• Adjustable differential of digital output Q1.
• Adjustable differential of digital output Q2.
• 24Vac controller supply voltage
• 24Vac two position control valves
• Remote set point adjustment via auxiliary analogue input X2.
• Day / night set points can be selected via time clock or switch.
Supplemental features
Control
Operating modes