User Manual

Siemens Building Technologies Application : 32 RWD82/32 – 04.2001
HVAC Products RWD82 1
RWD82/32
RWD82 Universal Controller
Application 32
Absolute limit control
Room temperature control
Hot water control valve - 3 pos
24Vac control system
Control ( P or PI )
Room temperature control
Proportional control ( 3 position ) of the hot water valve.
Absolute maximum and / or minimum limit control of the supply air.
Optional day / night set point adjustment .
S1
X1
X2
D1
Q1
Q2
CP
........RWD32.......
M1
HCV
RWD82/32
X1
X2
S1
Q1
Q2
HCV
PC
Room temperature sensor
Limit temperature sensor
Time clock or switch
Opening output for HCV
Closing output for HCV
3 - position hot water valve.
Personal computer
X1
Universal analogue input - main sensor
Auxiliary analogue input
Digital input
Digital output
Digital output
Communication port
TX2
T
Room temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
Adjustable proportional band of 3-position output Q1, Q2.
Integral action function selection and adjustment.
Timing of 3-position valve actuator
24Vac controller supply voltage
24Vac three position control valve
Duct temperature sensor can be selected as Ni1000, Pt1000, or active sensor.(X2)
Absolute maximum and / or minimum supply air temperature control.
Day / night set points can be selected via time clock or switch.
Supplemental features
Control
Operating modes