Siemens Building Technologies Application : 35 RWD82/35 – 04.2001
HVAC Products RWD82 1
RWD82/35
RWD82 Universal Controller
Application 35
Cascade control
Room temperature control
Hot water control valve - 3 pos
24Vac control system
Control ( P or PI )
Room temperature control
Proportional control ( 3 position ) of the hot water valve.
Cascade control .
Optional day / night set point adjustment .
S1
X1
X2
D1
Q1
Q2
CP
........RWD82.......
M1
HCV
RWD82/35
X1
X2
S1
Q1
Q2
HCV
PC
Room temperature sensor
Supply air temperature sensor
Time clock or switch
Opening output for HCV
Closing output for HCV
3 - position hot water valve.
Personal computer
X1
Universal analogue input - main sensor
Auxiliary analogue input
Digital input
Digital output
Digital output
Communication port
TX2
T
Room temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
Adjustable proportional band of 3-position output Q1, Q2.
Integral action function selection and adjustment.
Timing of 3-position valve actuator
24Vac controller supply voltage
24Vac three position control valve
Duct temperature sensor can be selected as Ni1000, Pt1000, or active sensor.(X2)
Cascade control of the supply air by the room temperature sensor.
Day / night set points can be selected via time clock or switch.
Supplemental features