User Manual
Siemens Building Technologies Application :44 RWD82/44 - 02.2001
HVAC Products RWD82 1
RWD82/44
RWD82 Universal Controller
Application 44
Compensation shift
Room temperature control
Hot water control valve
Chilled water control valve
Control ( 2 position )
Room temperature control
2 position control of the hot water control valve
2 position control of the chilled water control valve
Outside air compensation of the room temperature .
Optional day / night set point adjustment .
S1
X1
X2
D1
Q1
Q2
CP
........RWD32.......
M1
Q1
RWD32/44
X1
X2
S1
Q1
Q2
PC
Room temperature sensor
Outside air temperature sensor
Time clock or switch
2-position hot water valve
2-position chilled water valve.
Personal computer
X1
Universal analogue input - main sensor
Auxiliary analogue input
Digital input
Digital output
Digital output
Communication port
T
Q2
X2
T
• Room temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
• Adjustable dead zone with separate heating and cooling set points.
• Adjustable differential of digital output Q1.
• Adjustable differential of digital output Q2.
• 24Vac controller supply voltage
• 24Vac two position control valves
• Outside air temperature sensor can be selected as Ni1000, Pt1000, or active
sensor.(X2)
• Outside air compensation of the room temperature set point.
• Day / night set points can be selected via time clock or switch.
Supplemental features
Control
Operating modes