RWD82 Universal Controller
Application 53
Relative limit control
Room temperature control
Chilled water control valve
Chilled water pump output
Control two stage( 2 position )
Room temperature control
2 position control of the chilled water control valve
Digital output to energise chilled water pump ( dependent )
Relative maximum and / or minimum limit control of the supply air.
Optional day / night set point adjustment .
S1
X1
X2
D1
Q1
Q2
CP
........RWD82.......
M1
Q2
RWD82/53
X1
X2
S1
Q1
Q2
PC
Room temperature sensor
Limit temperature sensor
Time clock or switch
Chilled water pump
2-port two position chilled water valve
Personal computer
X1
Universal analogue input - main sensor
Auxiliary analogue input
Digital input
Digital output
Digital output
Communication port
T
Q1
T
X2
Room temperature sensor can be selected as Ni1000, Pt1000, or active sensor.
Combined adjustable differential of digital outputs Q1 and Q2.
Adjustable ON position of Q1.
24Vac controller supply voltage
24Vac two position control valve
Relative maximum and / or minimum supply air temperature control.
Day / night set points can be selected via time clock or switch.
Dependent mode for the two cooling outputs, meaning that there is one set point only,
one differential adjustment across combined Q1 and Q2, with the ON position of
Q1adjustable.